General Description: 22 AWG stranded (7x30) tinned copper conductors, PVC insulation, twisted pair, chrome PVC jacket. Physical Characteristics (Overall) Conductor AWG: # Conductors AWG Stranding Conductor Material 2 22 7x30 TC - Tinned Copper
Total Number of Conductors: 2 Insulation Insulation Material: Insulation Material Wall Thickness (in.) PVC - Polyvinyl Chloride 0.016
Outer Shield Outer Shield Material: Outer Shield Material Unshielded
Outer Jacket Outer Jacket Material: Outer Jacket Material Nom. Wall Thickness (in.) PVC - Polyvinyl Chloride .025
Overall Cable Overall Cabling Lay Length & Direction: Length (in.) Direction Twists (twist/ft) 1.500 Left Hand 8.000 Overall Cabling Color Code Chart: Number Color 1 Black 2 Red
Overall Nominal Diameter: 0.170 in.
Mechanical Characteristics (Overall) Operating Temperature Range: -20°C To +60°C Bulk Cable Weight: 15 lbs/1000 ft. Max. Recommended Pulling Tension: 18 lbs. Min. Bend Radius/Minor Axis: 1.750 in.
Applicable Specifications and Agency Compliance (Overall) Applicable Standards & Environmental Programs NEC/(UL) Specification: CMG NEC Articles: 800 CEC/C(UL) Specification: CMG EU Directive 2011/65/EU (ROHS II): Yes EU CE Mark: Yes EU Directive 2000/53/EC (ELV): Yes EU Directive 2002/95/EC (RoHS): Yes EU RoHS Compliance Date (mm/dd/yyyy): 04/01/2005 EU Directive 2002/96/EC (WEEE): Yes EU Directive 2003/11/EC (BFR): Yes
Page 1 of 2 08-26-2016
Detailed Specifications & Technical Data ENGLISH MEASUREMENT VERSION 8442 Multi-Conductor - High-Conductivity Copper Speaker Cable Twisted Jacketed Con
CA Prop 65 (CJ for Wire & Cable): Yes MII Order #39 (China RoHS): Yes Flame Test UL Flame Test: UL1685 FT4 Loading CSA Flame Test: FT4 Suitability Suitability - Indoor: Yes Plenum/Non-Plenum Plenum (Y/N): No Plenum Number: 88442, 82442
Electrical Characteristics (Overall) Nom. Inductance: Inductance (µH/ft) .2 Nom. Capacitance Conductor to Conductor: Capacitance (pF/ft) 30 Nom. Conductor DC Resistance: DCR @ 20°C (Ohm/1000 ft) 15.6 Max. Operating Voltage - UL: Voltage 300 V RMS Max. Recommended Current: Description Current 10C Temperature Rise 2.9 Amps per conductor @ 25°C ambient
Please note: This product is cut to the length and is not returnable.
Any amount of cable you order above the maximum continuous length of 1000 FT will be sent in separate pieces.